CONTROLS
CAMAC 187
DIGITAL OUT
ED-218567

CONTROLS HARDWARE RELEASE NO. 71.0

CAMAC 187 Module

Multiplexed Digital Output

Robert J. Ducar

Yurij S. Chernousko

October 15, 1990

CONTENTS

1  DESCRIPTION
2  CAMAC 187 OP CODES
3  CAMAC 187 MODULE - I/O ASSIGNMENTS
4  CAMAC 187 MODULE - FRONT PANEL
5  SPARES
6  DOCUMENTATION          
7  PALS DOCUMENTATION
8  ASSOCIATED DOCUMENTATION
   Appendix A

 

        1  DESCRIPTION
             The one-wide CAMAC 187  module  provides  digital  output
        control for applications requiring moderate amounts of control
        data.  The module furnishes 16  words  of  16  bit  data  with
        associated  address  and  strobe  lines for external latching.
        Some amount of digital monitor is also accepted.
             The module has been developed to effect  control  of  new
        mountain  ranges boxes that have been designed by Stan Tawzer.
        Each of these new boxes requires nearly three words of control
        data and provides three bits of status.  Accordingly, a single
        187 module could support up  to  five  mountain  range  boxes.
        Development   of   the   module  was  initiated  to  effect  a
        significant saving of  CAMAC  crate  slot  useage  that  would
        otherwise be necessary if already developed modules were used.
             The mountain range boxes do not  have  latch  capability.
        To  provide  necessary  demultiplexing and latch capability, a
        NIM  module  has  also  been   designed   to   fulfill   these
        requirements.  All connections between the 187 module, the NIM
        module, and the mountain range box(es) can  be  realized  with
        ribbon cable to facilitate implementation.
             All signals from the 187 module are active high  and  TTL
        compatible.   Address  and  data  for  each  output  word  are
        normally gated out for ten microseconds.   A  one  microsecond
        strobe  pulse  is  normally  issued  eight  microseconds after
        address and data are stable.  CAMAC read or  write  operations
        to  the  on-board cache memory may alter the time that data is
        stable before strobe.  Data will, however, be stable at  least
        five   microseconds  before  strobe.   Control  lines  may  be
        terminated with 1K ohm  resistors.   The  address  and  strobe
        outputs may be terminated with 100 ohms.
             Upon power-up or Z*S2 of the module, LAM is asserted  and
        the output strobe is inhibited until receipt of the F(16)A(15)
        or F(26)A(0) operation.  LAM will  also  be  asserted  if  the
        output strobe is inhibited by the F(24)A(0) operation.
             Monitor is effected by multiplexing a single bit of  data
        to  the 187 module for each unique state of the address lines.
        These bits will be latched, irrespective of the state of  LAM,
        and organized as a single 16 bit word of status.
 
        2  CAMAC 187 OP CODES
                All codes return module Q and X immediately. 
                This module may assert LAM.
            F(0) A(n)   Read Control Word n   n = 0 --> 15
            ---------   
                        R16 (MSB)        -         (LSB) R1
                        -----------------------------------
                        C15    -   Control Word n   -    C0
            F(1) A(0)   Read Combined External Status
            ---------   
                        R16 (MSB)        -         (LSB) R1
                        -----------------------------------
                        MSB   -   External Status    -   C0
            F(6) A(0)   Read Module Number 
            ---------
                        R16 - R10 | R9      -       R1
                        ------------------------------
                        |    0    | BB Hex, 187 Dec |
            F(7) A(0)  Dummy Read - No Data are Returned
            ---------
            F(16) A(n)  Write Control Word n   n = 0 --> 15
            ----------   
                        W16 (MSB)        -         (LSB) W1
                        -----------------------------------
                        C15    -   Control Word n   -    C0
            F(24) A(0)  Disable Output Strobe  (Set LAM)
            ----------
            F(26) A(0)  Enable Output Strobe   (Reset LAM)
            ----------
 
        3  CAMAC 187 MODULE - I/O ASSIGNMENTS
             Rear I/O:  36 Position Edge Connector   A = R    B = L
             POS  SIGNAL                POS  SIGNAL               
             ---  --------------        ---  ----------------
              1L  COMMON                 1R  COMMON
              2L  COMMON                 2R  COMMON
              3L  C15 (MSB)              3R  C14
              4L  C13                    4R  C12
              5L  C11                    5R  C10
              6L  C9                     6R  C8
              7L  C7                     7R  C6
              8L  C5                     8R  C4
              9L  C3                     9R  C2
             10L  C1                    10R  C0 (LSB)
             11L  COMMON                11R  COMMON
             12L  STROBE                12R  COMMON
             13L  COMMON                13R  COMMON
             14L  A8                    14R  COMMON
             15L  A4                    15R  Mn
             16L  A2                    16R  COMMON
             17L  A1                    17R  COMMON 
             18L  COMMON                18R  COMMON
 
                             Custom 187 I/O Board
                             ____________________
        A custom I/O pc board is available for the 187 module to adapt
        the  board  I/O  to  a  26  position  ribbon  cable connector.
        Assignment of this connector is as follows:
             POS  SIGNAL                POS  SIGNAL               
             ---  --------------        ---  ----------------
              1   C15 (MSB)              2   C14
              3   C13                    4   C12
              5   C11                    6   C10
              7   C9                     8   C8
              9   C7                    10   C6
             11   C5                    12   C4
             13   C3                    14   C2
             15   C1                    16   C0 (LSB)
             17   COMMON                18   STROBE
             19   COMMON                20   A8
             21   A4                    22   A2
             23   A1                    24   COMMON
             25   Mn                    26   COMMON
 
        4  CAMAC 187 MODULE - FRONT PANEL
                The CAMAC 187 module has the following front 
                panel features:
             N led:            Red (stretched)
             LAM led:          Red (not stretched)
             Output Active:    Green (stretched)
 
        5  SPARES
           A supply of CAMAC 187 operational spares is  maintained  on
        the second floor of the Linac Annex.
 
        6  DOCUMENTATION
               0812-ED-218567   Schematic
               0812-BD-218568   Artwork (RF-134)
               0812-BD-218569   Master Drawing
               0812-MD-34863    Outline Drawing
               0812-MC-35522    Front Panel Mechanical
               0812-MD-218570   Front Panel Silkscreen 
 
        7  PALS DOCUMENTATION
             Directory:   DEVL::USR$DISK3:[DUCAR.PALS]
             Filenames:  18710A.DAT  NAF Decoder  PLS173
                         18733A.DAT  Status Latch PLS153 (2 Required)
                                     Also loaded at Location #34
 
        8  ASSOCIATED DOCUMENTATION
               NIM Based Demultiplexer for Mountain Range Boxes
               0818-ED-218571   Schematic
               0818-BD-218572   Artwork (RF-135)
               0818-BD-218573   Master Drawing
               MRL22A.DAT       Latch Control PAL (2 Reqd)
        rjd:  DEVL::USR$DISK3:[DUCAR.DOC]CMC187.RNO 
 
                                 APPENDIX A
                         Mountain Range Box Specifics

        #BITS  Description
        -----  ----------------------------------------------------
          17   TD - Turn Delay  Range = 1 -> 99,999
           7   VTD - Vernier Turn Delay  LSB = 250 ps  Range = 68 ns
          11   BS - Bucket Number Select  Range = 1 -> 1113
           6   NS - Number of Sweeps   Range = 1 -> 63
           1   AS - Auto Stop = 1,  Free Run = 0
           1   Mn - Multiplexed Return Status:
               Associated with CW0 - Power On = 1,  Power Off = 0
               Associated with CW1 - Auto Stop = 1,  Free Run = 0
               Associated with CW2 - Local = 1,  Remote = 0
               Repeat pattern modulo 3.
               Associated with CW15 - 
                  NIM Latch Module Power On = 1, Power Off = 0

        Suggested Arrangement of bits in three control words:
        -----------------------------------------------------
                 CW0                  CW1                    CW2
         |-----------------|-------------------------|------------------|
         *  TD (less MSB)  *  0 BS | AS 0 0 TD(MSB)  *  0 0 NS | 0 VTD  *
         *      16 Bits    * 12 Bits  |  4 Bits      *  8 Bits | 8 Bits *

        Tawzer Suggested Arrangement of 60 position connector:
        ------------------------------------------------------
        1   3 to 19       22 to 32      38 to 44       48 to 53  54 to 57 60
        --------------------------------------------------------------------
           L - TD - M    L - BS - M    L - VTD - M    L - NS - M  S S C S   
        GG            GG            5G             3G                     3G

Security, Privacy, Legal