tds7000_set_trigger_level_c (ul_scopes)

	status.i4.v = tds7000_set_trigger_level_c(connect_info.g.v,
						  trigger.i4.v, level.r8.v)

	This routine sets the trigger level for a TDS7000 series scope.

	connect_info	scope connection structure created by a
			prior call to scope_connect
	trigger		trigger to set
			(TDS7000_TRIGGER_A -> trigger A (normal choice),
			 TDS7000_TRIGGER_B -> trigger B)
	level		desired trigger voltage level

	This function returns ACNET status values as follows:

	OK			success
	CLIB_SETLOCK		settings are locked
	CLIB_INVARG		invalid connection information passed
	CLIB_GENERIC_ERROR	error accessing scope information
	otherwise		other ACNET error

	This function requires the following include files:

	ul_scopes_h:scopelib_h, ul_scopes_h:tekdefs_h, acnet_errors_h

	Related functions:

	tds7000_get_id_string_c, tds7000_is_busy, tds7000_enable_channel_c,
	tds7000_set_sample_rate_c, tds7000_set_trace_length_c,
	tds7000_set_num_traces_c, tds7000_set_range_c, tds7000_set_offset_c,
	tds7000_set_trigger_type_c, tds7000_set_edge_trigger_params_c,
	tds7000_request_measurement, tds7000_reset_scope,
	tds7000_get_config_info, tds7000_get_trigger_config_info_c,
	tds7000_get_edge_trigger_config_info_c, tds7000_get_waveform_c,
	scope_connect, scope_disconnect, scope_info

	C/C++ usage:

	static const char	ip_name[] = "myscope.fnal.gov";
	int	status;
	int	trigger = TRIGGER;
	double	level = LEVEL;
	void	*connect_info;

	status = scope_connect(ip_name,&connect_info);

	status = tds7000_set_trigger_level_c(connect_info,trigger,level);

	status = scope_disconnect(&connect_info);