CONTROLS
CAMAC 183
DIGITAL OUTPUT
ED-218099

CONTROLS HARDWARE RELEASE NO. 51.2

CAMAC 183 Module

Digital Output

Active Low Outputs

Robert J. Ducar

April 14, 1986

CONTENTS

1  DESCRIPTION
2  CAMAC 183 OP CODES
3  CAMAC 183 MODULE - I/O ASSIGNMENTS
4  CAMAC 183 MODULE - FRONT PANEL
5  SPARES
6  DOCUMENTATION          
7  PALS DOCUMENTATION

 

          1  DESCRIPTION
             The one-wide CAMAC  183  module  provides  basic  digital
          output   control   facilities.    This   module  is  exactly
          equivalent to the CAMAC 182 module except  for  the  control
          line  drivers  being  active  low  rather  than  active high
          output.  Thirty-two individual control lines  are  provided,
          each  being  sourced  from a 75446 peripheral driver.  These
          control lines are well suited as relay drivers,  each  being
          capable of sinking up to 400 ma loads.  Each output is diode
          clamped to +24 volts for transient suppression.  Each output
          is  also  pulled-up  to  +24 volts with a 100K ohm resistor.
          The diode clamps and pull-up resistors may be  connected  to
          +5  volts  rather  than  to +24 volts by means of a soldered
          wire option.  Modules are normally  supplied  with  the  +24
          volt option.
             The control lines are addressable as two separate 16  bit
          words  for  monitor and control.  The setting of one or more
          output bits within one or the other control words is  a  two
          step  process.  The first part of the process is the writing
          of a 16 bit clock enable mask which defines the control bits
          that  may  be  altered.   The  data  contained in the second
          operation of writing the control word effect only those bits
          selected   by  the  previous  mask.   The  read/modify/write
          operation is thereby avoided.  The two step setting  process
          easily  accommodates  bit,  selected  bits, nibble, and byte
          control in applications where separate devices or parameters
          are controlled from a single module.
             Upon clear command or powering-up, all control lines  are
          set  to  the off state - non-conducting and high.  The clock
          enable masks are also set off.
 
          2  CAMAC 183 OP CODES
                  All codes return module Q and X immediately.
                  This module never asserts LAM.
              F(0) A(0)   Read Control Word 0
              ---------   
                          R16 (MSB)      -         (LSB) R1
                          ---------------------------------
                          C0-15  -  Control Word 0  -  C0-0
              F(0) A(1)   Read Control Word 1
              ---------   
                          R16 (MSB)      -         (LSB) R1
                          ---------------------------------
                          C1-15  -  Control Word 1  -  C1-0

              F(1) A(0)   Read CW0 Clock Enable Mask
              ---------
                          R16 (MSB)       -         (LSB) R1
                          ----------------------------------
                          C0-15  -  CW0 Clk En Mask  -  C0-0
              F(1) A(1)   Read CW1 Clock Enable Mask
              ---------
                          R16 (MSB)       -         (LSB) R1
                          ----------------------------------
                          C1-15  -  CW1 Clk En Mask  -  C1-0
 
              F(6) A(0)   Read Module Number 
              ---------
                          R16  - R9 | R8      -      R1
                          -----------------------------
                          |    0    | B7 Hex, 183 Dec |

              F(9) A(0)   Reset Module
              ---------
                          This command is a logical or with 
                          Z*S2 and power-up clear.  It resets 
                          the control outputs off and clock 
                          enable masks to zero.

              F(16) A(0)  Write Control Word 0
              ----------   
                          W16 (MSB)      -         (LSB) W1
                          ---------------------------------
                          C0-15  -  Control Word 0  -  C0-0
              F(16) A(1)  Write Control Word 1
              ----------   
                          W16 (MSB)      -         (LSB) W1
                          ---------------------------------
                          C1-15  -  Control Word 1  -  C1-0

              F(17) A(0)  Write CW0 Clock Enable Mask
              ----------
                          W16 (MSB)       -         (LSB) W1
                          ----------------------------------
                          C0-15  -  CW0 Clk En Mask  -  C0-0
              F(17) A(1)  Write CW1 Clock Enable Mask
              ----------
                          W16 (MSB)       -         (LSB) W1
                          ----------------------------------
                          C1-15  -  CW1 Clk En Mask  -  C1-0
              Example:  To set the low byte of Control Word 1 to 
                        $AB, the following commands are executed.
                                F(17) A(1)   $00FF
               
                                F(16) A(1)   $xxAB
 
          3  CAMAC 183 MODULE - I/O ASSIGNMENTS
               Rear I/O:  36 Position Edge Connector   A = R    B = L
               POS  SIGNAL            POS  SIGNAL               
               ---  --------------    ---  ----------------
                1L  Common             1R  Common
                2L  C1-15 (MSB)        2R  C0-15 (MSB)
                3L  C1-14   |          3R  C0-14   |
                4L  C1-13   |          4R  C0-13   |
                5L  C1-12   |          5R  C0-12   |
                6L  C1-11   |          6R  C0-11   |
                7L  C1-10   |          7R  C0-10   |
                8L  C1-9    |          8R  C0-9    |
                9L  C1-8    |          9R  C0-8    |
               10L  C1-7   CW1        10R  C0-7   CW0
               11L  C1-6    |         11R  C0-6    |
               12L  C1-5    |         12R  C0-5    |
               13L  C1-4    |         13R  C0-4    |
               14L  C1-3    |         14R  C0-3    |
               15L  C1-2    |         15R  C0-2    |
               16L  C1-1    |         16R  C0-1    |
               17L  C1-0  (LSB)       17R  C0-0  (LSB)
               18L  Common            18R  Common
 
          4  CAMAC 183 MODULE - FRONT PANEL
             The CAMAC 183 module has only a N led (Red, stretched) on
          the  front  panel  to  indicate  addressing  from  the CAMAC
          dataway.
 
          5  SPARES
             A supply of CAMAC 183 operational spares is maintained on
          the  second  floor of the Linac Annex.  Modules are normally
          supplied with the outputs diode-clamped and pulled-up to +24
          volts.
 
          6  DOCUMENTATION
               0812-ED-218099  Schematic
               0812-BD-218100  Artwork (RF-121)
               0812-BD-218101  Master Drawing
               0812-MD-34863   Outline Drawing
               0812-MC-35821   Front Panel Mechanical
               0812-MC-218103  Front Panel Silkscreen 
 
          7  PALS DOCUMENTATION
               Directory:   DEVL::USR$DISK3:[DUCAR.PALS]
               Filenames:  18201A.DAT  1st Level NAF Decoder  82S153
                           18205A.DAT  2nd Level NAF Decoder  82S153
          rjd:  DEVL::USR$DISK3:[DUCAR.DOC]CMC183.RNO